NLII-RH sensor

Room sensor NLII-RH is used to monitor the air quality inside buildings and power control ventilation (HVAC) systems according to current levels of air pollution. It is suitable for living rooms, bathrooms, warehouses, ateliers etc.

  • measures RH
  • 2x analog voltage/current output
  • 2x output relay – 2x NO/C
  • cascade switching
  • not required maintenance during operation
  • long life and stability

Description

Measurement of the relative humidity is based on the principle of capacitive polymer sensor.

Current air quality can be easily checked the by three LED indicators. Eco level means good indoor air quality needed to achieve a sense of well-being together with optimizing energy costs for heating or air conditioning.

ParameterValue 
Supply voltage range14 V – 40 V DC or 18 V – 30 V AC
Average consumption0,5W
Ingress protectionIP20
RH measuring range0 – 100 %RH
RH accuracy 20 – 80 %± 3 %RH
RH accuracy 0 – 100 %± 6 %RH
RH switching hysteresis5 %RH
T measuring range0 – 40°C
T accuracy± 0,4°C
T witching hysteresis relay0,5°C
Max. switching voltage250/30V AC / V DC
Max. switching current5/5A AC /A DC
Working humidity non condensing0 – 90 %RH
Working temperature no condensing0 to +50°C
Storage temperature-20 to +60°C
Expected lifetimemin. 10years
Dimensions90x80x31mm

Attached documents

Datasheet

Manual